The Fluke I1010 AC/DC Clamp-On Current Probe is a battery-powered dual Hall-effect, clamp-on probe that measures AC current to 700A and DC current to 1000A. It features a thumbwheel ZERO control that compensates for residual core magnetism, improving the range of DC measurements down to 1A. The probe has a maximum conductor size of one 1.18" (30mm) or two each 0.98" (25mm). It is accurate to n(2% of reading + 1A), 1A to 100A, DC to 62 Hz; n3%, 100A to 700A, DC and 48 Hz to 62 Hz; n5%, 700A to 1000A CD only. It is usable to 440 Hz.
Key Features:
- Battery-powered dual Hall-effect, clamp-on probe measures AC current to 700A, DC current to 1000A
- Thumbwheel ZERO control compensates for residual core magnetism, improving the range of DC measurements down to 1A
- Maximum conductor size: one 1.18" (30mm) or two each 0.98" (25mm)
- Accuracy: n(2% of reading + 1A), 1A to 100A, DC to 62 Hz; n3%, 100A to 700A, DC and 48 Hz to 62 Hz; n5%, 700A to 1000A CD only
- Usable to 440 Hz
Applications:
- Electrical troubleshooting
- Maintenance
- Repair
- Manufacturing
- Testing
Benefits:
- Clamp-on design allows for hands-free measurement
- Accurate measurements down to 1A
- Wide measurement range
- Long battery life
- Rugged construction
To learn more about the Fluke I1010 AC/DC Clamp-On Current Probe, please visit our website.